-
UPS Systems
- PCs and Servers to 1.5kVA
- Servers and Networks to 3kVA
- Comms Room UPS to 20kVA
- Datacentres 10-800kVA
- Rackmount 500VA-40kVA
- Modular Systems 25kW-1MW
- Models by Size 500VA-800kVA
- Models by Technology
- Extended Backup Times
- Single Phase 400VA-20kVA
- Three Phase 10-800kVA
- Containerised UPS Systems
- 120Vac US Systems
- Telecoms UPS
- Industrial Plants
- Marine and Offshore Systems
- UPS with an Energy Saving Eco Mode
- UPS with Super Capacitors
- UPS with Lithium-ion Batteries
- UPS with Flywheels
- Power Distribution
- Inverters/Chargers
- Battery Systems
- Voltage Management
- Energy Management
- Power/Energy Monitoring
- Renewable/Off-Grid Power
- Accessories
- Connectivity/Software
-
Eco Power Services
- Battery Testing
- Battery Installations
- Generator Services
- Load Bank Testing
- Project Management
- Removals and Recycling
- Remote Site Monitoring
- Repair and Refurbishment
- Site Surveys
- Technical Helpdesk
- UPS/Generator Rentals
- UPS/Generator Relocations
- UPS Installations
- UPS Maintenance Contracts
- UPS Repairs/Spares
- Warranties and Extensions
- Witness Testing
- Eco Power Projects
UPS Maintenance Bypass Switches
External UPS maintenance bypass switches allow uninterruptible power supplies to be isolated during UPS maintenance and general service work without disruption to the load.
Most UPS above 5kVA include some form of internal UPS maintenance bypass facility but an external device allows the UPS to be completely removed from the electrical circuit if required for upgrade or swap-out.
Our UPS maintenance bypass switches are designed to support the uninterruptible power supplies and brands we supply. Some of our bypasses are sourced directly from the UPS manufacturer and others are manufactured within the company. Custom designs are available including Castell interlocks, volt-free contact alarm signals, visual meters, local AC service engineer power sockets and parallel UPS installation support.
Some of the UPS maintenance bypasses in this collection have sockets for ‘plug and play’ installation and above 3kVA they will be hardwired, requiring electrical installation by a qualified electrical contractor.
It is very important to match to maximum input rating of the UPS to the bypass amperage rating. Each maintenance bypass in this collection shows the phases and Amperage rating as per the table below:
Numeric | Input Supply | Output Supply |
---|---|---|
11 | Single Phase | Single Phase |
31 | Three Phase | Single Phase |
33 | Three Phase | Three Phase |
Our engineering team includes certified electrical contractors allowing us to provide a complete ‘in-house’ electrical installation for any maintenance bypass and LV switchgear panel arrangement. In addition the EcoPowerSupplies design team can customise our bypass switches to meet your specification.
For further information on the UPS maintenance bypasses and LV switchgear we manufacture please call the Eco Power Projects team on 0800 612 7388, complete an enquiry form form or email us.
Displaying all 15 items
UPS Maintenance Bypasses Guide
The following table matches each of our maintenance bypasses to the relevant UPS. Remember to choose a wall mounted or rack mounted version to match your UPS installation format. Also ensure you purchase the right UPS bypass switch for your your input and output supply configuration.
Bypass | UPS Size |
---|---|
10A 11 | 700VA-1kVA |
16A 11 | 2.2-3kVA |
32A 11 | 5-6kVA |
63A 11* | 6.5-12kVA |
63A 31 | 6.5-15kVA |
63A 33 | 10-30kVA |
125A 11 | 27kVA |
125A 31 | – |
125A 33 | 40-80kVA |
200A 31 | – |
200A 33 | 120kVA |
250A 33 | 160kVA |
400A 33 | 250kVA |
400A+ | On application |
Note: * if these UPS are installed in a 3/1 (three phase input/single phase output configuration) the relevant 3/1 maintenance bypass must be selected. Please contact us if you need further information.
Above 250kVA switchgear panels are supplied.
UPS Maintenance Bypass Notes
Some uninterruptible power supplies include a built-in maintenance bypass facility. This allows the UPS to be serviced and maintained ‘in-situ’ without a risk down disruption to the connected loads or maintenance engineer themselves.
An external maintenance bypass switch of the type in this collection, allows the UPS to be fully isolated and powered down, without disruption to the load. This means that the UPS itself can then be fully powered down and removed safely for either an upgrade, swap out or board replacement on site.
Care has to be taken when selecting a UPS maintenance bypass to match the correct version (single or three phase) to the UPS and the correct rating. In addition the UPS should ideally be of the make-before-break variety (rather than the lower cost break-before-make type) to ensure that the connected loads do not see any break in supply when transferring from or to the output of the UPS.
Maintenance bypasses can be wall mounted, rack mounted or built into LV switchgear and distribution panels. They can also be integrated with sockets or hardwire terminals to provide a power distribution unit (PDU) arrangement.
Castell Interlock Options
Our UPS bypasses can be built with two types of optional Castell Interlocking arrangement.
Option 1 – a trapped Castell key with auxiliary contacts for connection to a UPS remote bypass signal with a Castell bolt on the external bypass switch. Turning the Castell key on the UPS maintenance bypass switch operates the AUX contact (N/O or N/C) and generates a remote bypass signal. The key is now free and can be used to release the interlock bolt on the bypass switch of the external UPS maintenance bypass switch. The UPS maintenance bypass switch has AUX contacts in series with the Castell AUX for remote bypass signalling.
Option 2 – a trapped Castell key solenoid which is released when a “UPS in bypass” signal is generated from the UPS (key free when UPS in bypass) and Castell bolt on the external maintenance bypass switch. This will require a 24Vdc Normally Open contact to close when the UPS is in bypass. This releases the Castell key and operates the AUX contact (N/O or N/C) to give a remote bypass signal to the UPS. The key is then free and can be used to release the interlock bolt on the maintenance bypass switch of the external UPS bypass switch. The switch also has AUX contacts in series with the Castell AUX for remote bypass signalling.